Toroidal transformers - Single phase Produced in compliance with EN 61 558 Total power 25VA to 1600VA Normalized voltages to 500V 50/60Hz Unnormalized voltages to 500V 50/60Hz Thermal insulation class E Transformer heating to 60°C Class of construction II Protection level IP 20 Surrounding temperature -10°C...+35°C Standard and nonstandard dimensions Realisation: - without the gripping possibility - with the pressure plate - with the sealed centre - sealed in the box to 800VA - another realisation As necessary – separation of windings with the shielding foil
| | Technické parametre: Výkon (VA) | D (mm) | H (mm) | L (mm) | Váha (kg) | Tepelné straty (W) | Pokles U pri ln (%) | Úèinnos» (%) | | 25 | 65 | 31 | 200 | 0,5 | 3,7 | 12,4 | 83,6 | | 40 | 72 | 32 | 200 | 0,6 | 4,8 | 10 | 85,7 | | 50 | 76 | 38 | 200 | 0,8 | 5,8 | 9,6 | 86,2 | | 63 | 76 | 39 | 200 | 0,8 | 7 | 9,5 | 86,6 | | 80 | 86 | 38 | 200 | 1,1 | 7,6 | 7,9 | 88,6 | | 100 | 87 | 40 | 200 | 1,1 | 9,4 | 8,1 | 88,7 | | 125 | 88 | 46 | 200 | 1,3 | 10,8 | 7,4 | 89,3 | | 160 | 109 | 41 | 200 | 1,7 | 11,8 | 6,1 | 90,3 | | 200 | 109 | 46 | 200 | 2 | 13,8 | 5,7 | 91,2 | | 250 | 123 | 45 | 200 | 2,5 | 16,4 | 5,4 | 91,9 | | 315 | 124 | 51 | 200 | 2,9 | 19,3 | 5,1 | 92,3 | | 400 | 133 | 61 | 200 | 3,9 | 20,8 | 4,1 | 93,2 | | 500 | 134 | 62 | 200 | 4,2 | 24,9 | 4,1 | 93,2 | | 630 | 135 | 74 | 200 | 5 | 30 | 3,9 | 93,7 | | 800 | 157 | 62 | 200 | 6,1 | 35 | 3,5 | 94,1 | | 1000 | 169 | 67 | 200 | 7,4 | 37 | 2,9 | 94,7 | | 1250 | 180 | 69 | 200 | 8,8 | 41,9 | 2,6 | 95,3 | | 1600 | 202 | 71 | 200 | 11,1 | 50,9 | 2,4 | 95,5 |
|